Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2015, 08:42 AM
  • D 0130_D 0129_11102015_Manual.mp4

Date
11/10/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P10068
Time
12:42 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6628
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0130
Downstream MH
D 0129
Dir. of Survey
Downstream
Length Surveyed
672.5 ft.
Total Length
672.5 ft.
Structural Index
5
Structural Quick
5“4Z
Structural Rating
2658
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
2662
Pipe schematic from manhole D 0130 to D 0129
MH: D 0130MH: D 0129downstream0 ft. MGO - General Observation - MISSING TILES 100% START 9:00 TO 3:000 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING BROKEN CORRODED BEYOUND REBAR8 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG13.7 ft. MGO - General Observation - MISSING TILES 30%13.9 ft. SRC - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG49.8 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR53.9 ft. MGO - General Observation - MISSING TILES 20%59.9 ft. MGO - General Observation - MISSING TILES 100%62.4 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR64.6 ft. SRC - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG67.2 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM72.4 ft. SAP - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM74.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR76.4 ft. SRC - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: YES - LONG80.7 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES90.7 ft. MGO - General Observation - MISSING TILES 80%111.6 ft. MGO - General Observation - MISSING TILES 10%123.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE165.9 ft. SAP - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO185.3 ft. MGO - General Observation - MISSING TILES 30%197 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR215.6 ft. MGO - General Observation - MISSING TILES 60% START226.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO268.1 ft. MGO - General Observation - MISSING TILES 100%275.2 ft. SRC - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM276.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR315.3 ft. MGO - General Observation - MISSING TILES 20%320.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE324.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR328.1 ft. MGP - General Photograph332.7 ft. SAP - Surface Aggregate Projecting, from 10 to 01 o'clock, within 8 inches of joint: NO356.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BETOUND REBAR375.2 ft. MGO - General Observation - MISSING TILES 20%398.8 ft. SAP - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO466.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES487.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES511.2 ft. MGO - General Observation - MISSING TILES 60%525.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR541.7 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES599 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR619.7 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES634.4 ft. MGO - General Observation - MISSINGTILES 20%646.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR672.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE672.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG672.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM672.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - MISSING BROKEN CORRODED BEYOUND REBAR672.5 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (34)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING BROKEN CORRODED BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING BROKEN CORRODED BEYOUND REBAR

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG

    8 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG

    13.9 ft. - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    49.8 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

  • General Observation - MISSING TILES 100%

    59.9 ft. - General Observation - MISSING TILES 100%

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    62.4 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG

    64.6 ft. - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

    67.2 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    72.4 ft. - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

    74.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

  • Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: YES - LONG

    76.4 ft. - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: YES - LONG

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

    80.7 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - MISSING TILES 10%

    111.6 ft. - General Observation - MISSING TILES 10%

  • Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO

    165.9 ft. - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    197 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • General Observation - MISSING TILES 60% START

    215.6 ft. - General Observation - MISSING TILES 60% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

    226.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING TILES 100%

    268.1 ft. - General Observation - MISSING TILES 100%

  • Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM

    275.2 ft. - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG CIRCUM

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    276.9 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    324.2 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • General Photograph

    328.1 ft. - General Photograph

  • Surface Aggregate Projecting, from 10 to 01 o'clock, within 8 inches of joint: NO

    332.7 ft. - Surface Aggregate Projecting, from 10 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BETOUND REBAR

    356.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BETOUND REBAR

  • Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO

    398.8 ft. - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    466.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    487.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    525.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

    541.7 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    599 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

    619.7 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    646.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

Observations (55)

DistanceCodeObservation
672.1SAMSEVERE
511.2MGOMISSING TILES 60%
2SRCLONG
525.7SRCCORRODED BEYOUND REBAR
276.9SRCCORRODED BEYOUND REBAR
0MGOMISSING TILES 100% START 9:00 TO 3:00
80.7SAP
53.9MGOMISSING TILES 20%
619.7SAP
123.9TFACTIVE
67.2SAPCIRCUM
487.6SRC
672.1SRCLONG
356.8SRCCORRODED BETOUND REBAR
398.8SAP
0MWL
0MGOMH CONN ACTIVE 9:00
646.1SRCCORRODED BEYOUND REBAR
185.3MGOMISSING TILES 30%
320.3TFACTIVE
268.1MGOMISSING TILES 100%
13.7MGOMISSING TILES 30%
165.9SAP
72.4SAPCIRCUM
0AMH1:20AM
215.6MGOMISSING TILES 60% START
541.7SAP
2SAMSEVERE
74.6SRCBEYOUND REBAR
64.6SRCLONG
49.8SRCCORRODED BEYOUND REBAR
672.1SRCCIRCUM
2SRCCIRCUM
59.9MGOMISSING TILES 100%
2SRCREBAR MISSING BROKEN CORRODED BEYOUND REBAR
275.2SRCLONG CIRCUM
226.2SRC
0MWM
672.1SRCMISSING BROKEN CORRODED BEYOUND REBAR
328.1MGP
466.4SRC
8SAPLONG
90.7MGOMISSING TILES 80%
13.9SRCLONG
315.3MGOMISSING TILES 20%
197SRCCORRODED BEYOUND REBAR
634.4MGOMISSINGTILES 20%
375.2MGOMISSING TILES 20%
111.6MGOMISSING TILES 10%
672.5AMH2:45AM
324.2SRCCORRODED BEYOUND REBAR
599SRCCORRODED BEYOUND REBAR
76.4SRCLONG
62.4SRCCORRODED BEYOUND REBAR
332.7SAP

Properties (6)

custom_field_three
CORRODED BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2015-11-10T00:42:44-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false