Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2015, 08:41 AM
Date
11/09/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P10064
Time
12:41 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6627
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0126
Downstream MH
D 0125
Dir. of Survey
Downstream
Length Surveyed
61 ft.
Total Length
61 ft.
Structural Index
5
Structural Quick
5D4A
Structural Rating
178
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
178
Pipe schematic from manhole D 0126 to D 0125
MH: D 0126MH: D 0125downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN OPEN 3:00 IN STACK SMALL METAL PIPE0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM2 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM2 ft. MGO - General Observation - MISSING TILES 40% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE25.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING30.7 ft. SRC - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO60.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish60.7 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish60.8 ft. MGO - General Observation - MISSING TILES 40% FINISH61 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (5)

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

    2 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • General Observation - MISSING TILES 40% START

    2 ft. - General Observation - MISSING TILES 40% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING

    25.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN MISSING

  • Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO

    30.7 ft. - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
2SRCLONG
2SRCCIRCUM
2MGOMISSING TILES 40% START
0MWL
2SAMSEVERE
60.6SAM
61AMH3:05AM
30.7SRC
60.6SRC
0MGOMH CONN OPEN 3:00 IN STACK SMALL METAL PIPE
60.7SRC
0MWM
60.8MGOMISSING TILES 40% FINISH
25.5SRCBROKEN MISSING
0AMH2:50AM

Properties (6)

custom_field_three
BROKEN-MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2015-11-09T00:41:56-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false