Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 11:31 AM
  • D 0131_D 0130_11062015_Manual.mp4

Date
11/06/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P10069
Time
3:31 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6623
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0131
Downstream MH
D 0130
Dir. of Survey
Downstream
Length Surveyed
674.5 ft.
Total Length
674.5 ft.
Structural Index
5
Structural Quick
5v4Z
Structural Rating
1937
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
1941
Pipe schematic from manhole D 0131 to D 0130
MH: D 0131MH: D 0130downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:50AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE2 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:00 START2 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM5.5 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM90.7 ft. MGO - General Observation - MISSING TILES 50%106.4 ft. MGO - General Observation - MISSING TILES 30%132.4 ft. MGO - General Observation - MISSING TILES 80% START135.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES171.6 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN MISSING171.6 ft. MGO - General Observation - MISSING TILES 100% START171.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM LONG187.9 ft. SAP - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM191.4 ft. SRC - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG221.3 ft. SAP - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM230.2 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO233.5 ft. SRC - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG236.9 ft. SAP - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM254.1 ft. MGO - General Observation - MISSING TILKES 50% START281.7 ft. MGO - General Observation - 100% MISSING TILES START362.6 ft. SAP - Surface Aggregate Projecting, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM399.1 ft. MGO - General Observation - MISSING TILES 70% START420.2 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM442.6 ft. MGO - General Observation - MISSING TILES 100% START494.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN564.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO610.2 ft. MGO - General Observation - MISSING TILES 10% START652.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM652.2 ft. MGO - General Observation - MISSING TILES 50% START674.1 ft. MGO - General Observation - MISSINGTILES 50% FINISH674.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish674.1 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish674.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish674.1 ft. MGO - General Observation - MH CONN ACTIVE 9:00674.5 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (27)

  • General Observation - MISSING TILES 100% 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00 START

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

    2 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    5.5 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

  • General Observation - MISSING TILES 50%

    90.7 ft. - General Observation - MISSING TILES 50%

  • General Observation - MISSING TILES 30%

    106.4 ft. - General Observation - MISSING TILES 30%

  • General Observation - MISSING TILES 80% START

    132.4 ft. - General Observation - MISSING TILES 80% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    135.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN MISSING

    171.6 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN MISSING

  • General Observation - MISSING TILES 100% START

    171.6 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM LONG

    171.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM LONG

  • Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    187.9 ft. - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG

    191.4 ft. - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG

  • Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    221.3 ft. - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO

    230.2 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG

    233.5 ft. - Surface Reinforcement Corroded, at 10 o'clock, within 8 inches of joint: NO - LONG

  • Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    236.9 ft. - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

  • General Observation - MISSING TILKES 50% START

    254.1 ft. - General Observation - MISSING TILKES 50% START

  • General Observation - 100% MISSING TILES START

    281.7 ft. - General Observation - 100% MISSING TILES START

  • Surface Aggregate Projecting, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    362.6 ft. - Surface Aggregate Projecting, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

  • General Observation - MISSING TILES 70% START

    399.1 ft. - General Observation - MISSING TILES 70% START

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

    420.2 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

  • General Observation - MISSING TILES 100% START

    442.6 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN

    494.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    564.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING TILES 10% START

    610.2 ft. - General Observation - MISSING TILES 10% START

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    652.2 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

Observations (38)

DistanceCodeObservation
420.2SAPCIRCUM
674.1MGOMISSINGTILES 50% FINISH
674.1SAM
132.4MGOMISSING TILES 80% START
187.9SAPCIRCUM
281.7MGO100% MISSING TILES START
674.1SRC
221.3SAPCIRCUM
135.6SRC
442.6MGOMISSING TILES 100% START
191.4SRCLONG
171.6SRCBROKEN MISSING
564.3SRC
674.1SRC
0AMH4:50AM
0MWM
230.2SAP
674.5AMH5:50AM
236.9SAPCIRCUM
233.5SRCLONG
106.4MGOMISSING TILES 30%
2SAMSEVERE
674.1MGOMH CONN ACTIVE 9:00
171.6MGOMISSING TILES 100% START
0MWL
2MGOMISSING TILES 100% 9:00 TO 3:00 START
171.6SRCCIRCUM LONG
254.1MGOMISSING TILKES 50% START
652.2SRCCIRCUM
494.1SRCBROKEN
2SRCLONG
610.2MGOMISSING TILES 10% START
399.1MGOMISSING TILES 70% START
5.5SAPCIRCUM
652.2MGOMISSING TILES 50% START
90.7MGOMISSING TILES 50%
362.6SAPCIRCUM
2SRCCIRCUM

Properties (6)

custom_field_three
CORRODED BROKEN REBAR-CIRCUM & LONG
custom_field_two
2
customer
LACSD
datetime
2015-11-06T03:31:19-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false