Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 11:26 AM
  • D 0132_D 0131_11062015_Manual.mp4

Date
11/06/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P10070
Time
3:26 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6623
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0132
Downstream MH
D 0131
Dir. of Survey
Downstream
Length Surveyed
283 ft.
Total Length
283 ft.
Structural Index
5
Structural Quick
5`4J
Structural Rating
1049
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
5
Overall Quick
Overall Rating
1056
Pipe schematic from manhole D 0132 to D 0131
MH: D 0132MH: D 0131downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MISSING TILES 100% START 9:00 TO 3:002 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG24.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - MISSING- BROKEN26.4 ft. MGP - General Photograph32 ft. MGO - General Observation - MISSING TILES30% START81.5 ft. MGO - General Observation - 100% MISSING TILES98.2 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - BROKEN TILES DEBRIE114.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO117.2 ft. MGO - General Observation - MISSING TILES 60% START151.5 ft. MGO - General Observation - MISSING TILES 90% START282.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM282.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - MISSING- BROKEN282.7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE282.7 ft. MGO - General Observation - MISSING TILES 90% FINISH282.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - LONG283 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (11)

  • General Observation - MISSING TILES 100% START 9:00 TO 3:00

    2 ft. - General Observation - MISSING TILES 100% START 9:00 TO 3:00

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG

    2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - MISSING- BROKEN

    24.5 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - MISSING- BROKEN

  • General Photograph

    26.4 ft. - General Photograph

  • General Observation - MISSING TILES30% START

    32 ft. - General Observation - MISSING TILES30% START

  • General Observation - 100% MISSING TILES

    81.5 ft. - General Observation - 100% MISSING TILES

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO - BROKEN TILES DEBRIE

    98.2 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - BROKEN TILES DEBRIE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    114.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING TILES 60% START

    117.2 ft. - General Observation - MISSING TILES 60% START

  • General Observation - MISSING TILES 90% START

    151.5 ft. - General Observation - MISSING TILES 90% START

Observations (21)

DistanceCodeObservation
2MGOMISSING TILES 100% START 9:00 TO 3:00
117.2MGOMISSING TILES 60% START
98.2DSZBROKEN TILES DEBRIE
32MGOMISSING TILES30% START
0MWL
151.5MGOMISSING TILES 90% START
282.7SRCCIRCUM
81.5MGO100% MISSING TILES
282.7SRCMISSING- BROKEN
26.4MGP
0AMH4:10AM
114.3SRC
282.7SAMSEVERE
0MWM
2SRCCIRCUM
282.7MGOMISSING TILES 90% FINISH
2SAMSEVERE
2SRCLONG
24.5SRCMISSING- BROKEN
282.7SRCLONG
283AMH4:45AM

Properties (6)

custom_field_three
CORRODED BROKEN REBAR CIRCUM & LONG
custom_field_two
2
customer
LACSD
datetime
2015-11-06T03:26:18-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false