Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 10:20 AM
Date
11/06/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P23006
Time
2:20 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6623
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D JOINT
Downstream MH
D 0227
Dir. of Survey
Downstream
Length Surveyed
4.6 ft.
Total Length
4.6 ft.
Structural Index
5
Structural Quick
5542
Structural Rating
33
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
33
Pipe schematic from manhole D JOINT to D 0227
MH: D JOINTMH: D 0227downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:002 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM MISSING PROJECTING2 ft. MGO - General Observation - MISSING TILES 100% START2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR2 ft. MGO - General Observation - MAG COAT 60% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE4.1 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish4.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish4.1 ft. MGO - General Observation - MAG COAT 60% FINISH4.1 ft. MGO - General Observation - MISSING TILES 100%FINISH4.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish4.6 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (2)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM MISSING PROJECTING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM MISSING PROJECTING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

Observations (16)

DistanceCodeObservation
2SRCLONG
4.2SAM
4.1SRC
0AMH2:20AM
2SRCCIRCUM MISSING PROJECTING
4.1SRC
0MWM
2MGOMISSING TILES 100% START
4.1MGOMAG COAT 60% FINISH
0MWL
2SRCCORRODED BEYOUND REBAR
0MGOMH CONN ACTIVE 9:00
2MGOMAG COAT 60% START
2SAMSEVERE
4.1MGOMISSING TILES 100%FINISH
4.6AMH2:35AM

Properties (6)

custom_field_three
CORRODED BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2015-11-06T02:20:21-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false