Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 09:01 AM
Date
11/06/2015
W/O
0531068
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P23007
Time
1:01 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6623
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151106MDM_JOINT_OUTFALL_D_UNIT_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0124
Downstream MH
D JOINT
Dir. of Survey
Downstream
Length Surveyed
722.9 ft.
Total Length
722.9 ft.
Structural Index
5
Structural Quick
5´4\
Structural Rating
3934
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
3934
Pipe schematic from manhole D 0124 to D JOINT
MH: D 0124MH: D JOINTdownstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:05AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE2 ft. MGO - General Observation - MAG COAT 60% START 8:00 TO 4:002 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM2 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR2 ft. MGO - General Observation - MISSING TILES 100% START 8:00 TO 4:002 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM14.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR14.8 ft. MGP - General Photograph - CORRODED BEYOUND REBAR25.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: NO - BEYOUND REBAR72.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - BEYOUND REBAR86.5 ft. SRP - Surface Reinforcement Projecting, from 09 to 04 o'clock, within 8 inches of joint: YES123.3 ft. MGO - General Observation - MISSING TILES 80%166.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR278.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - MISSING & PROJECTING351 ft. MGO - General Observation - MISSING TILES 50% START400.5 ft. MGO - General Observation - MISSING TILES 100% START461.2 ft. SRP - Surface Reinforcement Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO494.8 ft. MGO - General Observation - 20% MISSING TILES564.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - PROJECTING MISSING BEYOUND REAR CORRODED570.6 ft. MGP - General Photograph574.3 ft. MGP - General Photograph583.3 ft. MGP - General Photograph652.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR702.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - MISSING PROJECTING CORRODED BEYOUND REBAR722.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish722.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish722.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish722.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MISSING CORRODED BEYOUND REBAR722.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish722.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED BEYOUND REBAR722.7 ft. MGO - General Observation - MH CONN ACTIVE 9:00722.9 ft. AMH - Downstream Manhole, Survey Ends - 2:15AM

Observation photos (23)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM

  • General Observation - MISSING TILES 100% START 8:00 TO 4:00

    2 ft. - General Observation - MISSING TILES 100% START 8:00 TO 4:00

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    14.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • General Photograph - CORRODED BEYOUND REBAR

    14.8 ft. - General Photograph - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: NO - BEYOUND REBAR

    25.5 ft. - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: NO - BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

    72.5 ft. - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

  • Surface Reinforcement Projecting, from 09 to 04 o'clock, within 8 inches of joint: YES

    86.5 ft. - Surface Reinforcement Projecting, from 09 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - MISSING TILES 80%

    123.3 ft. - General Observation - MISSING TILES 80%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

    166.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - MISSING & PROJECTING

    278.5 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - MISSING & PROJECTING

  • General Observation - MISSING TILES 50% START

    351 ft. - General Observation - MISSING TILES 50% START

  • General Observation - MISSING TILES 100% START

    400.5 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO

    461.2 ft. - Surface Reinforcement Projecting, from 10 to 12 o'clock, within 8 inches of joint: NO

  • General Observation - 20% MISSING TILES

    494.8 ft. - General Observation - 20% MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - PROJECTING MISSING BEYOUND REAR CORRODED

    564.3 ft. - Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - PROJECTING MISSING BEYOUND REAR CORRODED

  • General Photograph

    570.6 ft. - General Photograph

  • General Photograph

    574.3 ft. - General Photograph

  • General Photograph

    583.3 ft. - General Photograph

  • Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    652.6 ft. - Surface Reinforcement Corroded, from 09 to 04 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - MISSING PROJECTING CORRODED BEYOUND REBAR

    702.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - MISSING PROJECTING CORRODED BEYOUND REBAR

Observations (37)

DistanceCodeObservation
25.5SRCBEYOUND REBAR
583.3MGP
722.5SAP
166.8SRCBEYOUND REBAR
2SAMSEVERE
123.3MGOMISSING TILES 80%
2MGOMAG COAT 60% START 8:00 TO 4:00
2SRVLONG
722.5SRV
2SAPMISSING REBAR
652.6SRCCORRODED BEYOUND REBAR
574.3MGP
2SRCLONG & CIRCUM
2SRCCORRODED BEYOUND REBAR
564.3SRCPROJECTING MISSING BEYOUND REAR CORRODED
72.5SRCBEYOUND REBAR
0AMH1:05AM
86.5SRP
2MGOMISSING TILES 100% START 8:00 TO 4:00
14.8SRCCORRODED BEYOUND REBAR
722.6SRCCORRODED BEYOUND REBAR
400.5MGOMISSING TILES 100% START
2SRVCIRCUM
722.9AMH2:15AM
0MWL
722.5SRCMISSING CORRODED BEYOUND REBAR
351MGOMISSING TILES 50% START
494.8MGO20% MISSING TILES
0MWM
278.5SRCMISSING & PROJECTING
722.7MGOMH CONN ACTIVE 9:00
722.4SRV
14.8MGPCORRODED BEYOUND REBAR
722.5SAM
702.6SRCMISSING PROJECTING CORRODED BEYOUND REBAR
570.6MGP
461.2SRP

Properties (6)

custom_field_three
CORRODED BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2015-11-06T01:01:58-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false