- Date
- 02/16/2016
- W/O
- 541748
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00244
- PipeID
- P02895
- Time
- 1:57 AM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3146
- Sewer Name
- 02 DISTRICT #2 MAIN TRUNK
- City
- COMMERCE, CA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 17
- Purpose
- Routine Assessment
- Project
- WO_541748_TV02091_DEC2015
- Sewer Type
- GRAVITY
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Upstream MH
- 02 0576
- Downstream MH
- 02 0575
- Dir. of Survey
- Downstream
- Length Surveyed
- 135.9 ft.
- Total Length
- 135.9 ft.
- Structural Index
- 3
- Structural Quick
- 3B00
- Structural Rating
- 39
- O&M Index
- 2
- O&M Quick
- 4132
- O&M Rating
- 67
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 106
Pipe schematic from manhole 02 0576 to 02 0575 Observation photos (4)

3.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

62.1 ft. - Obstacles Rocks, 25 %of cross sectional area, from 03 to 06 o'clock

105.1 ft. - Material Change, Clay tile (not vitrified clay)

125 ft. - Surface Reinforcement Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO