Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2016, 06:37 AM
  • 15 0056_15 0055_20160329_235425.mp4

Date
03/29/2016
W/O
563386
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11949
Time
11:37 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3300
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
WO_563386_TV15025_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0056
Downstream MH
15 0055
Dir. of Survey
Downstream
Length Surveyed
283.3 ft.
Total Length
283.3 ft.
Structural Index
3
Structural Quick
3C21
Structural Rating
68
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
180
Pipe schematic from manhole 15 0056 to 15 0055
MH: 15 0056MH: 15 0055downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00560 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES13.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"33 ft. CS - Crack Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES37.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"138.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"141.3 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES166 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES185 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start189.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish283.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK283.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish283.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0055283.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES

    33 ft. - Crack Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    141.3 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    167.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    185 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    283.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (27)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
240.9TFC
13.4TFC
88TFC
185CM
37.1TFC
189.5TFA
166TFA
283.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
138.6TFC
283.3DAGS
283.3AMH15 0055
167.7CM
0MWM
33CS
283.3MGOCOCKROACHES IN MANHOLE
141.3CM
0MWL
279.5CM
64.7TFC
114.9TFC
216.6TFC
0AMH15 0056
0MGOCOCKROACHES IN MANHOLE
5.8CM
267.4TFC
2DAGS

Properties (6)

additional_info
SC305426
custom_field_two
3
customer
LACSD
datetime
2016-03-29T23:37:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false