Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2016, 09:30 AM
  • 15 0062_15 0061_20160331_030138.mp4

Date
03/31/2016
W/O
563386
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11956
Time
2:30 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3301
Sewer Name
15 PUENTE TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563386_TV15025_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0062
Downstream MH
15 0061
Dir. of Survey
Downstream
Length Surveyed
416.4 ft.
Total Length
416.4 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
34
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
42
Pipe schematic from manhole 15 0062 to 15 0061
MH: 15 0062MH: 15 0061downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 00622 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start13.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES24 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.4 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES50.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.2 ft. CM - Crack Multiple, from 02 to 08 o'clock, within 8 inches of joint: YES229.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"253 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"296.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES297.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.6 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES384.3 ft. MGP - General Photograph - HOLE WITH REPAIR VISIBLE384.3 ft. HVV - Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - REPAIR VISIBLE390.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES397.4 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Start412.9 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Finish414.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish416.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0061416.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK416.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (12)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    13.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    25.4 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 08 o'clock, within 8 inches of joint: YES

    225.2 ft. - Crack Multiple, from 02 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    296.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    304.6 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • General Photograph - HOLE WITH REPAIR VISIBLE

    384.3 ft. - General Photograph - HOLE WITH REPAIR VISIBLE

  • Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - REPAIR VISIBLE

    384.3 ft. - Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - REPAIR VISIBLE

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    390.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Water Level, Sag in pipe, 50 %of cross sectional area, Start

    397.4 ft. - Water Level, Sag in pipe, 50 %of cross sectional area, Start

  • General Observation - COCKROACHES IN MANHOLE

    416.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (33)

DistanceCodeObservation
0MWL
279.6TF
300.6TFC
416.4AMH15 0061
384.3MGPHOLE WITH REPAIR VISIBLE
175.9TFC
151.7TF
416.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
397.4MWLS
416.4MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
297.9TB
253TFC
75.3TFC
0MWM
296.1CM
50.8TFC
24TFC
304.6FM
101.4TFC
414.6DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
229.3TFC
412.9MWLS
202.8TFC
125.3TFC
390.3CM
13.6CM
225.2CM
25.4FM
384.3HVVREPAIR VISIBLE
0AMH15 0062
2DAGS

Properties (6)

additional_info
SC305427
custom_field_two
3
customer
LACSD
datetime
2016-03-31T02:30:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false