Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2016, 07:53 AM
  • 15 0052_15 0051A_20160330_012407.mp4

Date
03/30/2016
W/O
563386
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11945
Time
12:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3300
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_563386_TV15025_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0052
Downstream MH
15 0051A
Dir. of Survey
Downstream
Length Surveyed
229 ft.
Total Length
229 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
129
O&M Index
2
O&M Quick
2H00
O&M Rating
94
Overall Index
2
Overall Quick
Overall Rating
223
Pipe schematic from manhole 15 0052 to 15 0051A
MH: 15 0052MH: 15 0051Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00520.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.7 ft. OBR - Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock95.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"146 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"229 ft. MSA - Survey Abandoned - DUE TO SETTLED DEPOSITS/DEBRIS229 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES229 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish229 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0.1 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock

    94.7 ft. - Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock

  • Survey Abandoned - DUE TO SETTLED DEPOSITS/DEBRIS

    229 ft. - Survey Abandoned - DUE TO SETTLED DEPOSITS/DEBRIS

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    229 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0MWM
229MSADUE TO SETTLED DEPOSITS/DEBRIS
146TFA
0MWL
0.1MGOCOCKROACHES IN MANHOLE
45TFA
95.4TFC
229DSZ
2DAGS
195.6TFC
12.3CM
71.8TFA
229CM
222.5TFC
121.8TFC
172.4TFA
0AMH15 0052
94.7OBR
229DAGS

Properties (6)

additional_info
SC305426
custom_field_two
5
customer
LACSD
datetime
2016-03-30T00:53:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false