Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2022, 06:52 PM
  • 03 0224_03 0223_08082022_121202.mp4

Date
08/08/2022
W/O
967253
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00387
PipeID
P04825
Time
11:52 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10352
Sewer Name
03 NORTH LONG BEACH TRUNK
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_967253_TV03158_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
12 in.
Upstream MH
03 0224
Downstream MH
03 0223
Dir. of Survey
Downstream
Length Surveyed
442.9 ft.
Total Length
442.9 ft.
Structural Index
4
Structural Quick
514G
Structural Rating
176
O&M Index
3
O&M Quick
413P
O&M Rating
382
Overall Index
3
Overall Quick
Overall Rating
558
Pipe schematic from manhole 03 0224 to 03 0223
MH: 03 0224MH: 03 0223downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 02242.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10.5 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start118.4 ft. B - Broken, from 09 to 11 o'clock, within 8 inches of joint: YES142.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start204.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish272.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES315.9 ft. CS - Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES364.5 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES381.2 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES384.9 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES440.6 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish440.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish442.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0223

Observation photos (8)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 09 to 11 o'clock, within 8 inches of joint: YES

    118.4 ft. - Broken, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    142.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    272.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

    315.9 ft. - Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    364.5 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    381.2 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    384.9 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
440.6DSC
142.7DAGS
442.9AMH03 0223
381.2CS
0MWL
272.8FL
315.9CS
364.5CS
440.6DAGS
0MWM
2.1FM
0AMH03 0224
118.4B
204.4FM
384.9CS
10.5DSC

Properties (7)

additional_info
630098080822062
custom_field_three
BROKEN, SEVERE FRACTURES
custom_field_two
1
customer
1
datetime
2022-08-08T11:52:21-07:00
documentation
PROPIPE
is_lateral_inspection
false