Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2022, 07:13 PM
  • 03 0223_03 0222_08082022_123257.mp4

Date
08/08/2022
W/O
967253
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00387
PipeID
P04824
Time
12:13 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10352
Sewer Name
03 NORTH LONG BEACH TRUNK
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_967253_TV03158_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
12 in.
Upstream MH
03 0223
Downstream MH
03 0222
Dir. of Survey
Downstream
Length Surveyed
443.4 ft.
Total Length
443.4 ft.
Structural Index
3
Structural Quick
4332
Structural Rating
24
O&M Index
2
O&M Quick
412P
O&M Rating
176
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 03 0223 to 03 0222
MH: 03 0223MH: 03 0222downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 02230 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE13.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start21.4 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES170.7 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES272.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES356.8 ft. FM - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES372.5 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES409.9 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES417.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES441.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish443.4 ft. AMH - Downstream Manhole, Survey Ends - 03 0222

Observation photos (9)

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE

    2 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    13.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    21.4 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    170.7 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    272.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    356.8 ft. - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    372.5 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    409.9 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    417.2 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
409.9FM
417.2CL
21.4FM
356.8FM
2CSAT MOUTH OF PIPE
13.7DAGS
0AMH03 0223
441.6DAGS
0MWM
0MWL
170.7CM
272.3CM
372.5CS
443.4AMH03 0222

Properties (7)

additional_info
630098080822062
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2022-08-08T12:13:30-07:00
documentation
PROPIPE
is_lateral_inspection
false