Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2022, 05:54 AM
  • 02 0861_02 0860_09082022_231147.mp4

Date
09/08/2022
W/O
972698
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00297
PipeID
P03428
Time
10:54 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10416
Sewer Name
02 OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTS 2&3
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_972698_TV02216_SEP2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
02 0860
Downstream MH
02 0861
Dir. of Survey
Upstream
Length Surveyed
637 ft.
Total Length
637 ft.
Structural Index
3
Structural Quick
5X3X
Structural Rating
1263
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1263
Pipe schematic from manhole 02 0860 to 02 0861
MH: 02 0860MH: 02 0861upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 08612.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish634 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start634.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start634.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start634.9 ft. MGO - General Observation - MAG COAT637 ft. MWM - Water Mark, 20 %of cross sectional area637 ft. MWL - Water Level, 20 %of cross sectional area637 ft. AMH - Downstream Manhole, Survey Begins - 02 0860

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2.1SAV
0MWM
3SRV
0MWL
631SRV
634.6SAV
631SSS
0AMH02 0860
637AMH02 0861
2.5SSS
2.1MGOMAG COAT

Properties (7)

additional_info
630074090822202
custom_field_three
AGGREGATE VISIBLE/REINFORCEMENT VISIBLE/SPALLING
custom_field_two
2
customer
1
datetime
2022-09-08T22:54:11-07:00
documentation
PROPIPE
is_lateral_inspection
false