Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2022, 09:24 AM
  • 02 0852_02 0851_09142022_024223.mp4

Date
09/14/2022
W/O
972698
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00297
PipeID
P03419
Time
2:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10419
Sewer Name
02 OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTS 2&3
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_972698_TV02216_SEP2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
15 in.
Upstream MH
02 0852
Downstream MH
02 0851
Dir. of Survey
Downstream
Length Surveyed
218.7 ft.
Total Length
218.7 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0852 to 02 0851
MH: 02 0852MH: 02 0851downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 08520 ft. MWL - Water Level, 10 %of cross sectional area3.6 ft. MGO - General Observation - MAG COAT3.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start218.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0851

Observation photos (2)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
218.7SRV
3.7SRV
0MGOCONNECTION AT MH 3 O'CLOCK
218.7SAP
0AMH02 0852
0MWL
3.7SAP
3.6MGOMAG COAT
218.7AMH02 0851

Properties (7)

additional_info
630074091322202
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2022-09-14T02:24:31-07:00
documentation
PROPIPE
is_lateral_inspection
false