Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2022, 08:41 AM
  • H 0599_H 0598_09122022_015850.mp4

Date
09/12/2022
W/O
967382
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00190
PipeID
P11020
Time
1:41 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10451
Sewer Name
H JOINT OUTFALL H - UNIT 8G
City
BALDWIN PARK
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_967382_TV15150_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0599
Downstream MH
H 0598
Dir. of Survey
Downstream
Length Surveyed
541.5 ft.
Total Length
541.5 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
525
O&M Index
2
O&M Quick
4A2U
O&M Rating
260
Overall Index
2
Overall Quick
Overall Rating
785
Pipe schematic from manhole H 0599 to H 0598
MH: H 0599MH: H 0598downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05992 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS2 ft. MGO - General Observation - MAG COAT13.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start479 ft. LL - Alignment Left, 25 %, Start536 ft. LL - Alignment Left, 25 %, Finish539.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish539.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish539.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish541.5 ft. AMH - Downstream Manhole, Survey Ends - H 0598541.5 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (5)

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start - DEBRIS

    2 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    541.5 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
2DSZDEBRIS
0MWL
2MGOMAG COAT
541.5AMHH 0598
479LL
16.7SAV
13.4SSS
539.9SSS
0MWM
539.9SAV
539.9DSZ
536LL
0AMHH 0599
541.5MGOCOCKROACHES IN MH

Properties (8)

additional_info
63
custom_field_three
SPALLING/VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2022-09-12T01:41:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27198