Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2022, 08:08 AM
  • 08 0305A_08 0305_09222022_012152.mp4

Date
09/22/2022
W/O
973084
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00352
Time
1:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10435
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_973084_TV08154_SEP2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
08 0305A
Downstream MH
08 0305
Dir. of Survey
Downstream
Length Surveyed
195.5 ft.
Total Length
195.5 ft.
Structural Index
4
Structural Quick
4332
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole 08 0305A to 08 0305
MH: 08 0305AMH: 08 0305downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0305A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area8.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"21.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"97.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish98.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"154.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"183.7 ft. H - Hole, from 11 to 12 o'clock, within 8 inches of joint: YES184.8 ft. H - Hole, at 12 o'clock, within 8 inches of joint: NO186 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES191.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish195.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0305195.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    98.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, from 11 to 12 o'clock, within 8 inches of joint: YES

    183.7 ft. - Hole, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: NO

    184.8 ft. - Hole, at 12 o'clock, within 8 inches of joint: NO

  • Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

    186 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
60TFC
21.9CM
0MWL
0AMH08 0305A
191.3FM
0MGOCONNECTION AT MH 9 O'CLOCK
183.7H
186B
184.8H
8.8TF
195.5AMH08 0305
108.8TFC
98.1FM
154.3TFC
195.5MGOCONNECTION AT MH 3 O'CLOCK
0MWM
97.2CM

Properties (7)

additional_info
630074092122203
custom_field_three
MULTIPLE FRACTURE'S/HOLE/BROKEN
custom_field_two
2
customer
1
datetime
2022-09-22T01:08:29-07:00
documentation
PROPIPE
is_lateral_inspection
false