Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2022, 09:58 AM
  • 08 0303_08 0302_09222022_030919.mp4

Date
09/22/2022
W/O
973084
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00349
Time
2:58 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10435
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_973084_TV08154_SEP2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
08 0303
Downstream MH
08 0302
Dir. of Survey
Downstream
Length Surveyed
220.5 ft.
Total Length
220.5 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 08 0303 to 08 0302
MH: 08 0303MH: 08 0302downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03030 ft. MWM - Water Mark, 20 %of cross sectional area3.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"65.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"133.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"170 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"209 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"220.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0302220.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
3.7FM
65.4TF
0MWL
133.8TF
170TF
220.5AMH08 0302
36.7TFC
220.5FM
209TF
0AMH08 0303
0MWM

Properties (7)

additional_info
630074092122203
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-09-22T02:58:47-07:00
documentation
PROPIPE
is_lateral_inspection
false