Wastewater/Activity/PacpInspection/1.0Sep 27, 2022, 09:18 AM
  • 15 0849_15 0848_9272022_023502.mp4

Date
09/27/2022
W/O
0972560
Weather
Dry
Operator/Surveyor
BRAR
Sewer ID
Z00594
PipeID
P12627
Time
2:18 AM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H 3212
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRE MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20220927SB_AR_SI_MAD_TR_SEC_3_2A
Material
NRCP
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
15 0849
Downstream MH
15 0848
Dir. of Survey
Downstream
Length Surveyed
204.3 ft.
Total Length
204.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3221
O&M Rating
9
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 0849 to 15 0848
MH: 15 0849MH: 15 0848downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15.0849 POST ROOT EVAL0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start70.9 ft. RML - Roots Medium Lateral, from 02 to 06 o'clock, 15 %, within 8 inches of joint: NO149.5 ft. RML - Roots Medium Lateral, from 12 to 05 o'clock, 5 %, within 8 inches of joint: NO196.2 ft. RFL - Roots Fine Lateral, from 02 to 05 o'clock204.3 ft. AOC - Drop Connection, Survey Ends - 15.0848204.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (9)

DistanceCodeObservation
0MWL
70.9RML
204.3AOC15.0848
149.5RML
204.3DAGS
196.2RFL
0AMH15.0849 POST ROOT EVAL
2DAGS
0MWM

Properties (9)

additional_info
U-0618-0703002249
custom_field_three
GREASE/LINED PIPE
custom_field_two
4
customer
LACSD
datetime
2022-09-27T02:18:25-07:00
documentation
BRAR, OBREGON, CASTILLO, OLIVER
is_lateral_inspection
false
lining
CIPP
year_laid
20020918