Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2022, 05:40 PM
  • 29 0303_29 0302_08102022_110616.mp4

Date
08/10/2022
W/O
967346
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01025
PipeID
P24315
Time
10:40 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10357
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_967346_TV29056_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0302
Downstream MH
29 0303
Dir. of Survey
Upstream
Length Surveyed
334.6 ft.
Total Length
334.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
330
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
334
Pipe schematic from manhole 29 0302 to 29 0303
MH: 29 0302MH: 29 0303upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 03032.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish47 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"67.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN99.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"102.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"151.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"154.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"203.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"206 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"250.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"253.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"296.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"300.1 ft. TFD - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: NO, 4" - 65% GREASE-BROKEN CAP300.1 ft. DNF - Deposits Ingress Fine, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: NO - FROM LATERAL332.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start332.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start334.6 ft. MWM - Water Mark, 10 %of cross sectional area334.6 ft. MWL - Water Level, 5 %of cross sectional area334.6 ft. AMH - Downstream Manhole, Survey Begins - 29 0302

Observation photos (2)

  • Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: NO, 4" - 65% GREASE-BROKEN CAP

    34.5 ft. - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: NO, 4" - 65% GREASE-BROKEN CAP

  • Deposits Ingress Fine,  10 %of cross sectional area, at 04 o'clock,  , within 8 inches of joint: NO - FROM LATERAL

    34.5 ft. - Deposits Ingress Fine, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: NO - FROM LATERAL

Observations (22)

DistanceCodeObservation
235.3TFC
0MWM
180.3TFC
81.4TFC
266.7TBOPEN
2SSS
2CM
332SSS
332CM
131.5TFC
128.6TFC
232.5TFC
37.7TFA
287.6TFC
284.4TFC
183.4TFC
34.5TFD65% GREASE-BROKEN CAP
0MWL
84.5TFC
334.6AMH29 0303
0AMH29 0302
34.5DNFFROM LATERAL

Properties (7)

additional_info
630098081022062
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2022-08-10T10:40:59-07:00
documentation
PROPIPE
is_lateral_inspection
false