Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2022, 08:10 PM
  • 29 0202_29 0201_08152022_132722.mp4

Date
08/15/2022
W/O
967346
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01025
PipeID
P24101
Time
1:10 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10364
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_967346_TV29056_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0202
Downstream MH
29 0201
Dir. of Survey
Downstream
Length Surveyed
311.7 ft.
Total Length
311.7 ft.
Structural Index
3
Structural Quick
3L2K
Structural Rating
314
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
436
Pipe schematic from manhole 29 0202 to 29 0201
MH: 29 0202MH: 29 0201downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02020 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start7.4 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES38.1 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES66.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4", 4"115.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"118 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"167.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"170.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"217.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"218.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES219.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"266.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"268.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"309 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish311.7 ft. AMH - Downstream Manhole, Survey Ends - 29 0201

Observation photos (3)

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    7.4 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    38.1 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    218.4 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
217.3TFA
115.7TFC
69.6TFA
219.5TFA
266.3TFC
170.1TFC
0MWM
309CM
38.1CM
7.4CM
2CM
118TFC
167.5TFC
218.4CM
0MWL
311.7AMH29 0201
0AMH29 0202
268.9TFC
309SSS
66.8TFC
2SSS
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
309DAGS
2DAGS

Properties (7)

additional_info
630098081522062
custom_field_three
CRACK MULTIPLE
custom_field_two
3
customer
1
datetime
2022-08-15T13:10:58-07:00
documentation
PROPIPE
is_lateral_inspection
false