Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2022, 04:32 AM
  • 05 2458_05 2457_08252022_214414.mp4

Date
08/25/2022
W/O
967376
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00457
PipeID
P20853
Time
9:32 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10297
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_967376_TV05334_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 2458
Downstream MH
05 2457
Dir. of Survey
Downstream
Length Surveyed
223.9 ft.
Total Length
223.9 ft.
Structural Index
4
Structural Quick
4400
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 2458 to 05 2457
MH: 05 2458MH: 05 2457downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 2458151.1 ft. FM - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES156.2 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES167.8 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES173.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start208 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish223.9 ft. AMH - Downstream Manhole, Survey Ends - 05 2457

Observation photos (4)

  • Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

    151.1 ft. - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    156.2 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    167.8 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    173.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
167.8FM
151.1FM
223.9AMH05 2457
0MWL
156.2FM
0AMH05 2458
208FM
173.3FM

Properties (7)

additional_info
630074082522201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-25T21:32:19-07:00
documentation
PROPIPE
is_lateral_inspection
false