Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2022, 04:48 AM
  • 05 0846_05 0845_08262022_000230.mp4

Date
08/25/2022
W/O
967376
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00457
PipeID
P06076
Time
9:48 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10297
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_967376_TV05334_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 0846
Downstream MH
05 0845
Dir. of Survey
Downstream
Length Surveyed
318.7 ft.
Total Length
318.7 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 0846 to 05 0845
MH: 05 0846MH: 05 0845downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 08467.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"108 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.1 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES179.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"314.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK318.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK318.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0845

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    108 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    156.1 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
318.7MGOCONNECTION AT MH 3 O'CLOCK
7.5FM
139.8TF
0MGOCONNECTION AT MH 9 O'CLOCK
199.4TF
0MGOCONNECTION AT MH 3 O'CLOCK
60.3TF
254.9TF
318.7AMH05 0845
0MWL
115.2TF
67.7TF
0MWM
156.1RFJ
237.2TF
179.5TF
227.1TF
318.6MGOCONNECTION AT MH 9 O'CLOCK
124.3TF
99.7TF
0AMH05 0846
239.5TF
314.3FM
108TB

Properties (7)

additional_info
630074082522201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-25T21:48:16-07:00
documentation
PROPIPE
is_lateral_inspection
false