Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 06:58 AM
  • B 0736_B 0735_08032022_001141.mp4

Date
08/02/2022
W/O
962038
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00111
PipeID
P09203
Time
11:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10263
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_962038_TV22165_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
B 0736
Downstream MH
B 0735
Dir. of Survey
Downstream
Length Surveyed
234.7 ft.
Total Length
234.7 ft.
Structural Index
3
Structural Quick
463G
Structural Rating
147
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
147
Pipe schematic from manhole B 0736 to B 0735
MH: B 0736MH: B 0735downstream0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07366.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.9 ft. TS - Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"131 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES173.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.6 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES, Start204.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish232.3 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES, Finish234.7 ft. AMH - Downstream Manhole, Survey Ends - B 0735234.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    110.9 ft. - Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    131 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    150.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES, Start

    204.6 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
234.7AMHB 0735
173.9TF
234.7MGOCONNECTION AT MH 3 O'CLOCK
6.3CM
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
204.9CM
204.6FM
232.3FM
0MWM
110.9TS
131TB
0MWL
150.9FL
0AMHB 0736
70.2TF

Properties (7)

additional_info
630098080222202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-02T23:58:48-07:00
documentation
PROPIPE
is_lateral_inspection
false