Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 08:21 AM
  • B 0728A_B 0728_08032022_014115.mp4

Date
08/03/2022
W/O
962038
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00111
PipeID
P09193
Time
1:21 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10263
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
DUARTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_962038_TV22165_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
B 0728A
Downstream MH
B 0728
Dir. of Survey
Downstream
Length Surveyed
340.2 ft.
Total Length
340.2 ft.
Structural Index
4
Structural Quick
4H3D
Structural Rating
254
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
4
Overall Quick
Overall Rating
255
Pipe schematic from manhole B 0728A to B 0728
MH: B 0728AMH: B 0728downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - B 0728A0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area9.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES9.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.3 ft. FC - Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES69.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES81.9 ft. FM - Fracture Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES118.4 ft. FM - Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES126.7 ft. FM - Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES130.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start130.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.9 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YESR337.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.2 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK340.2 ft. AMH - Downstream Manhole, Survey Ends - B 0728

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

    25.3 ft. - Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    69.9 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES

    81.9 ft. - Fracture Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

    118.4 ft. - Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES

    126.7 ft. - Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    130.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YESR

    280.9 ft. - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YESR

Observations (17)

DistanceCodeObservation
25.3FC
69.9FC
9.1FC
81.9FM
340.2MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
130.9FM
130.9CM
280.9RFJ
0MGOCONNECTION AT MH 9 O'CLOCK
118.4FM
9.1CM
337.4FM
340.2AMHB 0728
0AMHB 0728A
0MWM
126.7FM
0MWL

Properties (7)

additional_info
630098080222202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-03T01:21:16-07:00
documentation
PROPIPE
is_lateral_inspection
false