Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2022, 08:41 AM
  • B 0728_B 0727_08032022_015614.mp4

Date
08/03/2022
W/O
962038
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00111
PipeID
P09192
Time
1:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10263
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
DUARTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_962038_TV22165_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
B 0728
Downstream MH
B 0727
Dir. of Survey
Downstream
Length Surveyed
288.3 ft.
Total Length
288.3 ft.
Structural Index
3
Structural Quick
473J
Structural Rating
187
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole B 0728 to B 0727
MH: B 0728MH: B 0727downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - B 07286 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES138.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES225.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.5 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR252.8 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES259.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start259.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.3 ft. AMH - Downstream Manhole, Survey Ends - B 0727288.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK288.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    46.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    138.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    252.8 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    259.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
288.3AMHB 0727
252.8FM
0MWL
46.6FL
259.7FM
0MWM
259.7CM
288.3MGOCONNECTION AT MH 3 O'CLOCK
6CM
225.5TFC
288.3FM
138.8FL
252.5RFJ
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0AMHB 0728

Properties (7)

additional_info
630098080222202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-03T01:41:26-07:00
documentation
PROPIPE
is_lateral_inspection
false