Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2022, 09:24 AM
  • 30 0362_30 0361_08252022_023258.mp4

Date
08/25/2022
W/O
966854
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00854
PipeID
P17998
Time
2:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10296
Sewer Name
30 CLIFTON P.P. FORCE MAIN GRAVITY TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_966854_TV30011_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0361
Downstream MH
30 0362
Dir. of Survey
Upstream
Length Surveyed
173.2 ft.
Total Length
173.2 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 30 0361 to 30 0362
MH: 30 0361MH: 30 0362upstream0 ft. AMH - Upstream Manhole, Survey Ends - 30 03620.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish8.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES46.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.9 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish144.3 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start154.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start160.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES173.2 ft. MWM - Water Mark, 5 %of cross sectional area173.2 ft. AMH - Downstream Manhole, Survey Begins - 30 0361173.2 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (5)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    12.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    28.9 ft. - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    126.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    164.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
18.4CM
173CM
0MWM
12.3CL
38.3RFJ
28.9RFJ
164.7FM
0AMH30 0361
0MWL
173.2AMH30 0362
126.3TB

Properties (7)

additional_info
630074082422205
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-08-25T02:24:21-07:00
documentation
PROPIPE
is_lateral_inspection
false