Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2022, 08:04 PM
  • 29 0208_29 0207_08092022_132357.mp4

Date
08/09/2022
W/O
966940
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01026
PipeID
P24110
Time
1:04 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10355
Sewer Name
29 28TH STREET PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_966940_TV29123_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0208
Downstream MH
29 0207
Dir. of Survey
Downstream
Length Surveyed
303.5 ft.
Total Length
303.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 29 0208 to 29 0207
MH: 29 0208MH: 29 0207downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02082.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start17.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"40.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"63.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"91.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"114.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"142.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"165.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"193.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"216.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"244.2 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"267.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"303.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish303.5 ft. AMH - Downstream Manhole, Survey Ends - 29 0207

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
17.9TFC
244.2TFA
63.5TFA
0MWL
303.5DAGS
193.1TFC
91.5TFA
0MWM
40.7TFC
142.6TFC
216.1TF
267.3TFA
0AMH29 0208
303.5AMH29 0207
2.1DAGS
114.5TFC
165.4TFC

Properties (6)

additional_info
630098080922062
custom_field_two
3
customer
1
datetime
2022-08-09T13:04:38-07:00
documentation
PROPIPE
is_lateral_inspection
false