Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2022, 04:50 PM
  • 29 0206_29 0205_08092022_102324.mp4

Date
08/09/2022
W/O
966940
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01026
PipeID
P24108
Time
9:50 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10355
Sewer Name
29 28TH STREET PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_966940_TV29123_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0206
Downstream MH
29 0205
Dir. of Survey
Downstream
Length Surveyed
254.2 ft.
Total Length
254.2 ft.
Structural Index
4
Structural Quick
4232
Structural Rating
14
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 29 0206 to 29 0205
MH: 29 0206MH: 29 0205downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02060 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"62.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"90.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"113.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"140.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"147.9 ft. FM - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES162.9 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES164.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"192 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"203.7 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES214.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"226.8 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES242.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish254.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0205

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

    147.9 ft. - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

    162.9 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    203.7 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    226.8 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
0MWL
162.9FS
113.8TFC
90.7TFC
242.6TFC
140.8TF
147.9FM
254.2AMH29 0205
0MWM
2.1DAGS
39.8TFC
62.8TFC
164.2TFC
226.8CM
252.1DAGS
214.5TFC
192TFC
203.7FM
0AMH29 0206
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630098080922062
custom_field_three
CRACKS. FRACTURES
custom_field_two
2
customer
1
datetime
2022-08-09T09:50:46-07:00
documentation
PROPIPE
is_lateral_inspection
false