Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2022, 06:26 AM
  • 03 0038_03 0037_08242022_233757.mp4

Date
08/24/2022
W/O
967254
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00366
PipeID
P05058
Time
11:26 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10293
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_967254_TV03159_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
03 0038
Downstream MH
03 0037
Dir. of Survey
Downstream
Length Surveyed
322.9 ft.
Total Length
322.9 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
141
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
141
Pipe schematic from manhole 03 0038 to 03 0037
MH: 03 0038MH: 03 0037downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 03 00388.2 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.2 ft. TSA - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start123.1 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.9 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TSA - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"302.2 ft. TSA - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"318.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0037

Observation photos (5)

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    8.2 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    64.2 ft. - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    84.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    123.1 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    164.9 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
0MWM
8.2TS
318.8CM
0MWL
164.9TS
64.2TSA
322.9AMH03 0037
0MGOCONNECTION AT MH 9 O'CLOCK
84.5CM
245.7TF
123.1TS
0AMH03 0038
199.5TSA
302.2TSA

Properties (7)

additional_info
630074082422202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-08-24T23:26:39-07:00
documentation
PROPIPE
is_lateral_inspection
false