Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2022, 04:36 AM
  • C 0686_C 0113_08242022_214713.mp4

Date
08/24/2022
W/O
967263
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00126
PipeID
P24969
Time
9:36 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10292
Sewer Name
C JOINT OUTFALL C - UNIT 4A
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_967263_TV03150_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
C 0686
Downstream MH
C 0113
Dir. of Survey
Downstream
Length Surveyed
103.6 ft.
Total Length
103.6 ft.
Structural Index
4
Structural Quick
4B35
Structural Rating
67
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
75
Pipe schematic from manhole C 0686 to C 0113
MH: C 0686MH: C 0113downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 06860 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 11 O'CLOCK (CONNECTS TO LINE @ 9 O'CLK.)2 ft. MWL - Water Level, 5 %of cross sectional area2 ft. MWM - Water Mark, 20 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish67.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish98.4 ft. MCU - Camera Underwater, Start - SAG IN PIPE.103.6 ft. MSA - Survey Abandoned - CAMERA UNDER WATER103.6 ft. MCU - Camera Underwater, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    9.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
95.3FM
103.6MSACAMERA UNDER WATER
0AMHC 0686
3.1CM
103.6MCU
28.3FM
9.8TB
2MWL
98.4MCUSAG IN PIPE.
67.8TFA
2MWM
28.3CM
0MGOACTIVE CONNECTION AT MH 11 O'CLOCK (CONNECTS TO LINE @ 9 O'CLK.)

Properties (7)

additional_info
630074082422201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-24T21:36:55-07:00
documentation
PROPIPE
is_lateral_inspection
false