Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 07:17 AM
  • 18 0701A_18 0701_05192022_002924.mp4

Date
05/19/2022
W/O
951939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14552
Time
12:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10155
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
WO_951939_TV18053_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0701A
Downstream MH
18 0701
Dir. of Survey
Downstream
Length Surveyed
242 ft.
Total Length
242 ft.
Structural Index
2
Structural Quick
2H00
Structural Rating
92
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
92
Pipe schematic from manhole 18 0701A to 18 0701
MH: 18 0701AMH: 18 0701downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0701A10.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 10"11 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start242 ft. AMH - Downstream Manhole, Survey Ends - 18 0701242 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (8)

DistanceCodeObservation
0MWL
242AMH18 0701
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0AMH18 0701A
11SSS
10.3TF
242SSS

Properties (7)

additional_info
630074051822202
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2022-05-19T00:17:46-07:00
documentation
PROPIPE
is_lateral_inspection
false