Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 07:29 AM
  • 18 0701_18 0700_05192022_004031.mp4

Date
05/19/2022
W/O
951939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14551
Time
12:29 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10155
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
WO_951939_TV18053_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0701
Downstream MH
18 0700
Dir. of Survey
Downstream
Length Surveyed
402.8 ft.
Total Length
402.8 ft.
Structural Index
2
Structural Quick
3D2O
Structural Rating
232
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
232
Pipe schematic from manhole 18 0701 to 18 0700
MH: 18 0701MH: 18 0700downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07013 ft. MGO - General Observation - MAG COAT3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start284.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start402 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0700402.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    284.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
402SSS
3MGOMAG COAT
402.8AMH18 0700
0MWM
402.8SAP
0MWL
0AMH18 0701
402.8MGOCONNECTION AT MH 9 O'CLOCK
3SSS
284.3SAP

Properties (7)

additional_info
630074051822202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-05-19T00:29:51-07:00
documentation
PROPIPE
is_lateral_inspection
false