Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2022, 05:47 AM
  • 18 0792_18 0791_05172022_225302.mp4

Date
05/17/2022
W/O
951939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14650
Time
10:47 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10100
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_951939_TV18053_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0792
Downstream MH
18 0791
Dir. of Survey
Downstream
Length Surveyed
155.3 ft.
Total Length
155.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0792 to 18 0791
MH: 18 0792MH: 18 0791downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 07920 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area4.1 ft. MGO - General Observation - MAG COAT8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish155.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK155.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0791

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH18 0792
155.3MGOCONNECTION AT MH 9 O'CLOCK
4.1MGOMAG COAT
8SAV
0MWM
0MWL
61.7SAV
155.3AMH18 0791

Properties (7)

additional_info
630074051722202
custom_field_three
SURFACE AGGREGATE VISABLE HROUGHOUT THE LINE
custom_field_two
3
customer
1
datetime
2022-05-17T22:47:52-07:00
documentation
PROPIPE
is_lateral_inspection
false