Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2022, 05:53 AM
  • 18 0791_18 0790_05172022_230040.mp4

Date
05/17/2022
W/O
951939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14649
Time
10:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10100
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_951939_TV18053_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0791
Downstream MH
18 0790
Dir. of Survey
Downstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
104
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
104
Pipe schematic from manhole 18 0791 to 18 0790
MH: 18 0791MH: 18 0790downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07910 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start265 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0790265.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (8)

DistanceCodeObservation
265.6AMH18 0790
265SSS
0MWM
265.6MGOCONNECTION AT MH 9 O'CLOCK
2.2MGOMAG COAT
3SSS
0AMH18 0791
0MWL

Properties (7)

additional_info
630074051722202
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2022-05-17T22:53:30-07:00
documentation
PROPIPE
is_lateral_inspection
false