Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2022, 07:08 AM
  • 18 0768_18 0767_05182022_002435.mp4

Date
05/18/2022
W/O
951939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14627
Time
12:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10100
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_951939_TV18053_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0768
Downstream MH
18 0767
Dir. of Survey
Downstream
Length Surveyed
205.3 ft.
Total Length
205.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0768 to 18 0767
MH: 18 0768MH: 18 0767downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07680 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT26.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start205.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish205.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK205.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0767

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
205.3SAV
205.3MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0AMH18 0768
0MWL
2.2MGOMAG COAT
205.3AMH18 0767
26.7SAV

Properties (7)

additional_info
630074051722202
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2022-05-18T00:08:08-07:00
documentation
PROPIPE
is_lateral_inspection
false