Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2022, 06:39 AM
  • 01 0207_01 0206_08102022_235404.mp4

Date
08/10/2022
W/O
967226
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01249
Time
11:39 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10276
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_967226_TV01011_AUG2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0207
Downstream MH
01 0206
Dir. of Survey
Downstream
Length Surveyed
349.1 ft.
Total Length
349.2 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0207 to 01 0206
MH: 01 0207MH: 01 0206downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02070 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.4 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES38.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.8 ft. RML - Roots Medium Lateral, at 10 o'clock, 45 %, within 8 inches of joint: NO105.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"131 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"149.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES218 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"325.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"347 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0206349.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    4.4 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

    216.3 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
105.8RML
271.7TF
265.9TFA
0AMH01 0207
149.2TF
349.2AMH01 0206
111.2TF
105.8TF
131TF
54.5TF
2.2SAP
274.5TF
203.6TFA
38.9TF
0MGOCONNECTION AT MH 9 O'CLOCK
325.6TF
349.2MGOCONNECTION AT MH 9 O'CLOCK
4.4CC
218TF
0MWM
0MWL
216.3RFJ
347SAP

Properties (7)

additional_info
630074081022202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-08-10T23:39:53-07:00
documentation
PROPIPE
is_lateral_inspection
false