Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2022, 08:36 AM
  • 01 0229_01 0228_08152022_015015.mp4

Date
08/15/2022
W/O
967226
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01271
Time
1:36 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10284
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_967226_TV01011_AUG2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
01 0229
Downstream MH
01 0228
Dir. of Survey
Downstream
Length Surveyed
297.7 ft.
Total Length
297.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0229 to 01 0228
MH: 01 0229MH: 01 0228downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02292.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"85 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"190.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0228297.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
2.2SAP
142.1TF
0MWL
0MWM
64.2TF
238.1TF
86.2TFA
180.1TF
0AMH01 0229
230.6TF
190.3TF
297.7AMH01 0228
71.6TF
139.8TF
85TF
295.3SAP
28.6TF
202.7TF
233TF
185.4TF
297.7MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630074081522003
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-08-15T01:36:31-07:00
documentation
PROPIPE
is_lateral_inspection
false