Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2022, 10:28 AM
  • 01 0219_01 0218_08122022_034732.mp4

Date
08/12/2022
W/O
967226
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01261
Time
3:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10281
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_967226_TV01011_AUG2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0219
Downstream MH
01 0218
Dir. of Survey
Downstream
Length Surveyed
299 ft.
Total Length
299 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0219 to 01 0218
MH: 01 0219MH: 01 0218downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02190 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"183.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"212 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"294.4 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES295.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299 ft. AMH - Downstream Manhole, Survey Ends - 01 0218299 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    294.4 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
2.7SAP
0MWL
0AMH01 0219
249.6TF
299AMH01 0218
0MGOCONNECTION AT MH 9 O'CLOCK
212TF
295.2SAP
158.5TF
62.4TF
268.8TB
299MGOCONNECTION AT MH 9 O'CLOCK
57.3TF
103.1TF
247.5TF
98.2TF
214.4TF
0MWM
108.1TF
294.4FM
183.8TF
260.1TF

Properties (7)

additional_info
630074081122203
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-08-12T03:28:07-07:00
documentation
PROPIPE
is_lateral_inspection
false