Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2022, 08:42 AM
  • 01 0211_01 0210_08112022_015905.mp4

Date
08/11/2022
W/O
967226
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01253
Time
1:42 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10276
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_967226_TV01011_AUG2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0211
Downstream MH
01 0210
Dir. of Survey
Downstream
Length Surveyed
343.7 ft.
Total Length
343.7 ft.
Structural Index
4
Structural Quick
4232
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 01 0211 to 01 0210
MH: 01 0211MH: 01 0210downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02110 ft. MWM - Water Mark, 30 %of cross sectional area2.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES60.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES237.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"310.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"317.2 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES340.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish343.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0210343.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    22 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    205.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    317.2 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
237.4TF
310.7TF
340.6SAP
155.6TFA
0MWL
22FL
2.4SAP
205.8FM
60.8TF
118.7TF
75.8TF
0AMH01 0211
151.7TF
343.7AMH01 0210
111.1TF
187.1TF
70.9TF
343.7MGOCONNECTION AT MH 9 O'CLOCK
273.1TF
278.1TF
0MWM
202.2TF
192.3TF
317.2FM

Properties (7)

additional_info
630074081022202
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-08-11T01:42:03-07:00
documentation
PROPIPE
is_lateral_inspection
false