Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2022, 05:10 AM
  • E 0045_E 0044_08172022_222609.mp4

Date
08/17/2022
W/O
967135
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11272
Time
10:10 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10286
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_967135_TV01123_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0045
Downstream MH
E 0044
Dir. of Survey
Downstream
Length Surveyed
415.9 ft.
Total Length
415.9 ft.
Structural Index
3
Structural Quick
523P
Structural Rating
425
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
425
Pipe schematic from manhole E 0045 to E 0044
MH: E 0045MH: E 0044downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00450 ft. MWM - Water Mark, 25 %of cross sectional area2.6 ft. MGO - General Observation - MAG COAT2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES8.7 ft. SRV - Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES175.3 ft. MGO - General Observation - POSSIBLE HANGING REINFORCEMENT VISIBLE @ APPROX. 10 O'CLK.415.9 ft. AMH - Downstream Manhole, Survey Ends - E 0044415.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK415.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish415.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    3.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES

    8.7 ft. - Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
3.2SAP
415.9AMHE 0044
2.6MGOMAG COAT
3.2SRV
0MWL
0AMHE 0045
175.3MGOPOSSIBLE HANGING REINFORCEMENT VISIBLE @ APPROX. 10 O'CLK.
415.9MGOCONNECTION AT MH 9 O'CLOCK
8.7SRV
0MWM
415.9SSS
415.9SAP
2.8SSS

Properties (7)

additional_info
630074081722201
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2022-08-17T22:10:50-07:00
documentation
PROPIPE
is_lateral_inspection
false