Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2022, 09:01 AM
  • E 0038_E 0037_08182022_020613.mp4

Date
08/18/2022
W/O
967135
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11265
Time
2:01 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10286
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_967135_TV01123_AUG2022
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0038
Downstream MH
E 0037
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole E 0038 to E 0037
MH: E 0038MH: E 0037downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00382.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

    2.1 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observations (8)

DistanceCodeObservation
2.1MGOMAG COAT
2.1SAP
0MWL
0MWM
2.1SRV
0AMHE 0038
2.1SSS
2.1MSAVIEW OF D/S SIPHON FROM U/S MH

Properties (7)

additional_info
630074081722201
custom_field_three
AGGREGATE PROJECTING/SPALLING/REINFORCEMENT VISIBL
custom_field_two
2
customer
1
datetime
2022-08-18T02:01:52-07:00
documentation
PROPIPE
is_lateral_inspection
false