Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2022, 04:28 AM
  • E 0033_E 0031_08182022_215435.mp4

Date
08/18/2022
W/O
967135
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11259
Time
9:28 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10287
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_967135_TV01123_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
E 0033
Downstream MH
E 0031
Dir. of Survey
Downstream
Length Surveyed
320.3 ft.
Total Length
320.3 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
320
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
320
Pipe schematic from manhole E 0033 to E 0031
MH: E 0033MH: E 0031downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00330 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"142.3 ft. MGO - General Observation - POSSIBLE REINFORCEMENT PROJECTING @ 9 - 10 O'CLOCK.320.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.3 ft. AMH - Downstream Manhole, Survey Ends - e 0031 zoomed in

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
142.3MGOPOSSIBLE REINFORCEMENT PROJECTING @ 9 - 10 O'CLOCK.
2.1SSS
0MWM
0AMHE 0033
320.2SSS
320.2SAP
37.2TFA
2.1MGOMAG COAT
0MWL
320.3AMHe 0031 zoomed in
2.1SAP

Properties (7)

additional_info
630074081822201
custom_field_three
AGGREGATE, REINFORCEMENT(?) PROJECTING/SPALLING.
custom_field_two
2
customer
1
datetime
2022-08-18T21:28:23-07:00
documentation
PROPIPE
is_lateral_inspection
false