Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2022, 09:48 AM
  • 22 0328_22 0327_08292022_030710.mp4

Date
08/29/2022
W/O
967060
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00795
PipeID
P16615
Time
2:48 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10345
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_967060_TV22188_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0328
Downstream MH
22 0327
Dir. of Survey
Downstream
Length Surveyed
588.2 ft.
Total Length
588.2 ft.
Structural Index
3
Structural Quick
5V3V
Structural Rating
1170
O&M Index
2
O&M Quick
2V00
O&M Rating
234
Overall Index
3
Overall Quick
Overall Rating
1404
Pipe schematic from manhole 22 0328 to 22 0327
MH: 22 0328MH: 22 0327downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 03280 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"218 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"283.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"397.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"519.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"585.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish585.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish585.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish585.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish588.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE588.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0327

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    588.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
2SAP
324.3TBA
585.4SSS
0AMH22 0328
0MWL
588.2MGOCOCKROACHES IN MANHOLE
585.4DAGS
397.9TB
2DAGS
585.4SRV
283.9TB
2SSS
585.4SAP
218TBA
519.6TB
0MWM
6.3TBA
2SRV
588.2AMH22 0327

Properties (7)

additional_info
630098082922001
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-29T02:48:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false