Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2022, 10:07 AM
  • 22 0327_22 0326_08292022_032636.mp4

Date
08/29/2022
W/O
967060
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00795
PipeID
P16614
Time
3:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10345
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_967060_TV22188_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0327
Downstream MH
22 0326
Dir. of Survey
Downstream
Length Surveyed
598.4 ft.
Total Length
598.4 ft.
Structural Index
3
Structural Quick
5S3W
Structural Rating
1100
O&M Index
2
O&M Quick
2W00
O&M Rating
238
Overall Index
3
Overall Quick
Overall Rating
1338
Pipe schematic from manhole 22 0327 to 22 0326
MH: 22 0327MH: 22 0326downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 22 03272 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start157.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"164 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"596.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish596.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish596.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish596.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish598.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0326598.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE598.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    92.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    598.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
598.4AMH22 0326
598.4MGOCOCKROACHES IN MANHOLE
2SAP
164TB
0MWM
596.3SAP
596.3SRV
92.6SRV
2DAGS
0MWL
244.7TB
0MGOCOCKROACHES IN MANHOLE
596.3SSS
2SSS
285.8TBA
157.9TBA
598.4MGOCONNECTION AT MH 3 O'CLOCK
596.3DAGS
57.5TB
0AMH22 0327

Properties (7)

additional_info
630098082922001
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-29T03:07:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false