Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2022, 10:53 AM
  • 22 0326_22 0325_08292022_041150.mp4

Date
08/29/2022
W/O
967060
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00795
PipeID
P16613
Time
3:53 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10345
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_967060_TV22188_AUG2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0326
Downstream MH
22 0325
Dir. of Survey
Downstream
Length Surveyed
632.4 ft.
Total Length
632.4 ft.
Structural Index
3
Structural Quick
5V3X
Structural Rating
1210
O&M Index
2
O&M Quick
2X00
O&M Rating
252
Overall Index
3
Overall Quick
Overall Rating
1462
Pipe schematic from manhole 22 0326 to 22 0325
MH: 22 0326MH: 22 0325downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 03262 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start47.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start263.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"406.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"536.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"619.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"630.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish630.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish630.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish630.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish632.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0325632.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    632.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
263.3TBA
619.6TFC
536.8TFC
0MWM
406.5TBA
0MWL
47.9SRV
630.1DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
2SSS
632.4AMH22 0325
632.4MGOCOCKROACHES IN MANHOLE
630.1SSS
2SAP
0AMH22 0326
2DAGS
630.1SAP
630.1SRV

Properties (7)

additional_info
630098082922001
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-08-29T03:53:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false