Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2022, 10:44 AM
  • B 1073_B 1072_07252022_041457.mp4

Date
07/25/2022
W/O
961719
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00923
PipeID
P23039
Time
3:44 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9990
Sewer Name
B JOINT OUTFALL B - UNIT 1C REPLACEMENT
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
WO_961719_TV02421_JUL2022
Sewer Type
Gravity
Material
RGRCP-PTL
Shape
Circular
Height
78 in.
Width
78 in.
Upstream MH
B 1073
Downstream MH
B 1072
Dir. of Survey
Downstream
Length Surveyed
996.7 ft.
Total Length
996.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2g00
O&M Rating
396
Overall Index
2
Overall Quick
Overall Rating
396
Pipe schematic from manhole B 1073 to B 1072
MH: B 1073MH: B 1072downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 10730 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start994 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish996.7 ft. AMH - Downstream Manhole, Survey Ends - B 1072

Observations (6)

DistanceCodeObservation
2DAGS
0MWL
0AMHB 1073
0MWM
996.7AMHB 1072
994DAGS

Properties (8)

additional_info
630098072522001
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-07-25T03:44:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
FACTORY