Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2022, 05:33 AM
  • G 0209_G 0208_08082022_224934.mp4

Date
08/08/2022
W/O
962071
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01180
PipeID
P25573
Time
10:33 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10267
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_962071_TV01122_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
G 0209
Downstream MH
G 0208
Dir. of Survey
Downstream
Length Surveyed
320.8 ft.
Total Length
320.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole G 0209 to G 0208
MH: G 0209MH: G 0208downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 02090 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK5.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start30.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"317.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 3"319.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish320.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK320.8 ft. AMH - Downstream Manhole, Survey Ends - G 0208

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
68.8TFC
0MWM
317.5TFC
0AMHG 0209
5.9CM
0MWL
319.2CM
117.4TFC
219.3TFC
320.8MGOCONNECTION AT MH 9 O'CLOCK
303.3TFC
165.7TFC
0MGOCONNECTION AT MH 9 O'CLOCK
30.1TF
320.8AMHG 0208
244.5TFC
264.7TFC

Properties (7)

additional_info
630078080822201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-08-08T22:33:41-07:00
documentation
PROPIPE
is_lateral_inspection
false