Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2022, 07:44 AM
  • G 0200_G 0199_08052022_010526.mp4

Date
08/05/2022
W/O
962071
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01180
PipeID
P01105
Time
12:44 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10350
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_962071_TV01122_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
G 0200
Downstream MH
G 0199
Dir. of Survey
Downstream
Length Surveyed
358.6 ft.
Total Length
358.6 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
412[
O&M Rating
284
Overall Index
2
Overall Quick
Overall Rating
288
Pipe schematic from manhole G 0200 to G 0199
MH: G 0200MH: G 0199downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 02000 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start13.5 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start216.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES219.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES358.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish358.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish358.6 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK358.6 ft. AMH - Downstream Manhole, Survey Ends - G 0199

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    216.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    219.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
2.4DAGS
0MWL
0MWM
13.5DSC
0AMHG 0200
219.1CL
358.2DSC
358.6MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
358.2DAGS
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
358.6AMHG 0199
216.1CL

Properties (7)

additional_info
630098080422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-08-05T00:44:59-07:00
documentation
PROPIPE
is_lateral_inspection
false