Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2022, 09:12 AM
  • 01 0264_01 0263_08172022_022501.mp4

Date
08/17/2022
W/O
967125
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01310
Time
2:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10285
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_967125_TV01205_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0264
Downstream MH
01 0263
Dir. of Survey
Downstream
Length Surveyed
337.2 ft.
Total Length
337.2 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
264
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
264
Pipe schematic from manhole 01 0264 to 01 0263
MH: 01 0264MH: 01 0263downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02640 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK3.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. MGO - General Observation - ABANDONED MH95.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN183.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish337.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK337.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0263

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    11 ft. - General Observation - ABANDONED MH

Observations (16)

DistanceCodeObservation
183.4TF
0MWL
243.5TFC
0AMH01 0264
115.5TF
337.2MGOCONNECTION AT MH 3 O'CLOCK
334.9FM
0MWM
11MGOABANDONED MH
276.5TF
337.2AMH01 0263
197.8TF
0MGOCONNECTION AT MH 3 O'CLOCK
95.2TFC
3.9FM
155TFUNKNOWN

Properties (7)

additional_info
630074081622201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-17T02:12:18-07:00
documentation
PROPIPE
is_lateral_inspection
false