Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2022, 06:14 AM
  • 01 0244_01 0243_08162022_232747.mp4

Date
08/16/2022
W/O
967125
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01289
Time
11:14 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10285
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_967125_TV01205_AUG2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
01 0244
Downstream MH
01 0243
Dir. of Survey
Downstream
Length Surveyed
307.2 ft.
Total Length
307.2 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0244 to 01 0243
MH: 01 0244MH: 01 0243downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02440 ft. MWL - Water Level, 10 %of cross sectional area3.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"3.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES10.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish36.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.7 ft. TSC - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"268 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK307.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0243

Observation photos (5)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    3.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    36.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    127.7 ft. - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    133.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (24)

DistanceCodeObservation
33.5TFC
78.5TF
36.6CM
268TFC
119.4TF
0MWM
133.3TB
177.8TF
220.7TFC
39.3TFC
228.8TF
127.7TSC
115.3TF
36.6FM
139.5TF
79.7TF
10.4CM
0AMH01 0244
307MGOCONNECTION AT MH 3 O'CLOCK
3.6TFC
3.7CL
307.2AMH01 0243
306.9FM
0MWL

Properties (7)

additional_info
630074081622201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-08-16T23:14:18-07:00
documentation
PROPIPE
is_lateral_inspection
false